Submitted by: Michael Del Greco, New Jersey Home Inspector Lic GI 0121, President of Accurate Inspections, Inc, a New Jersey home inspection company Todays homes need considerably more power than homes did just a few years ago.
We barely had hand-held hairdryers two decades ago. Numerous electrical services are obsolete.
In addition to the frustration of not having enough power, overloads on the electrical
service present a serious fire hazard.
To figure out how much current a home needs, you have to know the size of the
electrical service and the wattage of the equipment present. Knowing how a single-
phase service delivers the current to 120- and 240-volt circuits is also helpful. (Single
phase is the typical residential service.)
There are two 120-volt poles, which are the parts of the panel box that receive power
from the utility company. To energize a 120-volt branch circuit, you only use one of
these poles. As you add 120-volt circuits, you alternate with the right and left poles.
The 240-volt circuits use both 120-volt poles to service large appliances like a clothes
dryer, water heater, range/oven, and central air conditioner.
The following is a rule of thumb to help determine the service requirements for a
house:
1) Figure out the square footage of the living area.
2) Multiply the square footage of the living area by three watts for the lighting and
small appliance loads.
3) Calculate the total wattage used by the major electric appliances (e.g., dryer,
range/oven, water heater, central air conditioner, and electric heat). Figure the first
10,000 watts at 100% and the remaining wattage at 40%.
4) Add these figures together and divide by 240. The answer should reflect your
necessary amperage or service size.
If your maximum usage is close to or above the rated amperage of the service, you
should consult a licensed electrician for your best options.
Here is an example of a typical house situation that you can use as a reference:
120-Volt Circuits 240-Volt Circuits
(Load is shared by two poles) (Load is drawn off both poles)
Lighting & Small Appliance Wattage at 120 Volts
Actual Lighting 1,500
Toaster 1,000
Hair Dryer 1,500
Refrigerator 400
Microwave 800
Coffee Maker 800
Iron 1,000
Dishwasher 1,500
Washing Machine 600
Garbage Disposal 1,500
Approx.Sub Total 9,600
Major Appliance Wattage at 240 Volts
Range/Oven (all elements) 15,000
Water Heater 4,500
Dryer 4,800
Heat Pump 5,000
Heat Pump Back-up 15,000
Approx. Total for Major Appliances 44,300
The 9,600 watts distributed to both 120-Volt poles converts this figure to 4,800 watts
at 240 volts.
240-Volt Major Appliances -44,300
120-Volt Appliances (converted) - 4,800
Total wattage =49,100
The first 10,000 watts at 100% =10,000
Balance at 40% demand (39,100 x 40%) =15,640
Net wattage necessary =25,640
25,640 divided by 240 = 106.84 amps.
The service size should accommodate 107 amps. This means you would need a 125-amp service. The 150-amp service is a more likely choice and somewhat standard size.
Visions of the numbers listed above may have brought about bad memories from Jr. High math class, but figuring out your amperage is an interesting task and really not difficult.
Information provided by Michael Del Greco, New Jersey Home Inspector Lic. GI 0121, American Society of Home Inspectors Member 102273, Pesident of Accurate Inspections, Inc. A West Paterson New Jersey Home Inspection firm.
Spam emails More free articles Related articles
|
More related feeds |
Why am I friends with her? My thought- More POWER to ya! I could never do it but Im sure if she works hard enough she can suceed- but it didnt stop there- she goes on to tell me for 30 minutes about how the people at this college want her SO BAD and they will ...The Details Every women who gives birth is tough because it is not an easy thing, but those that do it natural, all I can say is more power to ya! It definitely made me know for sure that I will never have a kid without an epidural if I have a ... More quotes from UA employees Palin power abuse…. ya think? • Captain Cranky won’t be turning on Channel 9 • If you had 30 years seniority and were captain of a 737, wouldn’t you be pissed as well? • Did you want me to help you or do it for you? ... “Altdorf lies undefended! Bring the pain.” Lets see ya all do this in a couple months when the population(even at odd hours) is more “Robust”.And of course the sploits have been fixed. Even if more people are in t4, it doesn’t stop 3am raids from being successful. ... I walk through the valley of the shadow of digg Then again so are stories from arstechnica, msn, nytimes, latimes, livescience, cnn, discovery, nationalgeographic, huffingtonpost, gizmodo, lifehacker, theonion, forbes, usatoday etc etc - if subbed by a power digger will pop more ... What ya hidin' It shows more abuse of power, how lying is the norm for her, and how Sarah Palin when backed into a corner and to protect her family to the death, will fake a pregnancy (you can buy fake pregnant bellies online, ya know…makes for a good ... More power to ya! Do what you have to do. I'm so... More power to ya! Do what you have to do. I'm so happy that SOMETHING is working out. PSC GRANTS ALABAMA POWER RATE INCREASES! SUSAN PARKER SEEMS TO BE ... ONCE AGAIN, Do NOT fuss about your rates going up with Alabama Power. I told you all back in 2005/2006 election that Susan Parker was accepting funds funneled through PACS that were associated with REGULATED UTILITIES!! Nope, ya just ... More Power to Ya A&B Electric is helping fix an electrical problem today by running a new wire to the meter. The wire stopped working in what the electricians believe was a failure caused by corrosion or a collapse in the conduit. ... Here’s Your Towel What we really had better do is get back to our normal, every-day lives and do what we were meant to do: make more pies. While our betters, those capable of the nuance necessary to conduct politics, carry on without our gross, ...
|
|
|
|